Leak Prevention & Detection of MV Gas-Insulated RMU Switchgear
2026-10-12 For SF6-insulated Ring Main Units (RMU) or GIS, the leakage rate requirement depends on whether the gas compartment is classified as a closed pressure system or a sealed pressure system under IEC standards. 1. IEC 62271-1 (General HV Switchgear Standard) IEC 62271-1 defines: Gas system type Maximum SF6 leakage rate Closed pressure system ≤ 0.5% per year Sealed pressure system Typically designed for ≤ 0.1% per year For a closed pressure system, the standard specifies a maximum relative leakage rate of 0.5%/year for SF6 and SF6 mixtures. The time between gas replenishments must be at least 10 years. For a sealed pressure system, IEC does not directly state a fixed maximum percentage, but notes […]